Refrigerant certification

Required evacuation levels

Pick the appliance, the job and when the recovery machine was made, and get the level the rule requires before the appliance is opened or scrapped, with the reason.

Find the required level

High-pressure (R-22)

10 inches of mercury vacuum

Before a major repair, a high-pressure appliance with a full charge of 200 pounds or more must reach 10 inches of mercury vacuum when the recovery equipment was made on or after 15 November 1993.

Verify the level is reached before the appliance is opened.

The table for major repairs and disposal

ApplianceEquipment before 15 Nov 1993On or after 15 Nov 1993
Very high-pressure0 in Hg vacuum0 in Hg vacuum
High-pressure, under 200 lb0 in Hg vacuum0 in Hg vacuum
High-pressure, 200 lb or more4 in Hg vacuum10 in Hg vacuum
Medium-pressure, under 200 lb4 in Hg vacuum10 in Hg vacuum
Medium-pressure, 200 lb or more4 in Hg vacuum15 in Hg vacuum
Low-pressure25 mm Hg absolute25 mm Hg absolute

Small appliances, motor vehicle air conditioners and similar appliances follow their own rules.

Pressure classes

ClassSaturated liquid at 104 FExamples
Low-pressureSaturated liquid below 45 psia at 104 FR-11, R-123, R-113, R-245fa
Medium-pressure45 to 170 psia at 104 FR-114, R-124, R-12, R-134a, R-500
High-pressure170 to 355 psia at 104 FR-22, R-407A, R-407C, R-410A, R-502
Very high-pressureA critical temperature below 104 F, or above 355 psia at 104 FR-13, R-23, R-503, R-508A, R-508B

Try 3 test questions

Question 1Evacuation levels
A technician recovers from a 120 lb R-22 system with a recovery machine made in 1992 before replacing the compressor. What level is required?
Question 2Evacuation levels
A lab's ultra-low-temperature system uses R-23, a very high-pressure refrigerant. Before a major repair, what level must it reach with a new recovery machine?
Question 3Small appliance recovery rules
A freezer's nameplate lists a 20-ounce charge. Its compressor will not run, and the recovery equipment was made in 2010. What is the least the technician may recover?

Next step

Questions people ask

What vacuum is required before opening an R-22 system?

R-22 is a high-pressure refrigerant. With recovery equipment made on or after 15 November 1993, a system under 200 pounds goes to 0 inches of mercury vacuum and one of 200 pounds or more to 10 inches, before a major repair or disposal.

What about a repair that is not major?

If no evacuation is planned afterwards, medium-, high- and very high-pressure appliances go to no higher than 0 psig, and low-pressure appliances are pressurized to no higher than 0 psig. An oil change allows up to 5 psig.

How much must be recovered from a small appliance?

With recovery equipment made on or after 15 November 1993: 90 percent if the appliance's compressor works, 80 percent if it does not. With older equipment, 80 percent. Reaching 4 inches of mercury vacuum also meets the rule.

What counts as a major repair?

Removing the compressor, condenser, evaporator or an auxiliary heat exchange coil, or uncovering an opening of more than 4 square inches of flow area for more than 15 minutes.